    So talking about circuit breaker voltage ratings for two seemingly identical three-pole circuit breakers:

    ▪️600V
    ▪️600Y/347V

    My understanding is that the second “slash rated” breaker isn’t rated to handle the voltages on a 600V delta system, only on a solidly-grounded wye system (the 347V to neutral/ground, with 600V between any phases).

    In a grounded wye system the highest voltage during interruption seen across one breaker pole is 347. Across two poles line to line would be 300 per pole. (300 * 2 =600)

    In a delta system with no ground, if there’s one ground fault on a phase before the breaker (line side), and another ground fault occurs on a different phase after the breaker (load side), that -one pole- connecting them would need to interrupt fault current at 600V.

    💬 2🔄 0⭐ 7

Replies

  • Oct 7, 2026, 6:43 PM

    Also:

    347V times root-3 is 600V. You’ve got three phases 120° apart from each other. Vector math stuff. Phasors.

    💬 0🔄 0⭐ 3
  • 💬 0🔄 0⭐ 2
  • 💬 0🔄 0⭐ 1
  • Oct 7, 2026, 6:49 PM

    @DeltaWye yeah 400/690 is incredibly rare here too. Basically it's 230/400 from bigger houses, right up to industrial plants that have say bigger than 500kW motors which jump to 3.3 or 6.6 kV

    💬 0🔄 0⭐ 2
  • Oct 7, 2026, 7:44 PM

    @PatrickHerd Ah yeah there’s a lot of 4160V, 6900, and for big stuff I’ve seen as high as 13.8kV.

    OLD stuff 2400V is the standard. That could be like early 1900s era. @KronoGarrett

    💬 0🔄 0⭐ 1
  • 💬 0🔄 0⭐ 0
  • Oct 8, 2026, 1:36 AM

    @DeltaWye That is correct. It is not rated to handle the 600V L-G fault. Can handle a 600V fault, but only across two phases so the voltage can split across two poles of the breaker.

    Sometimes it'll have a rating for the straight corner-grounded 600V and a higher interrupting slash rating.

    💬 0🔄 0⭐ 0