    Quick look at the details here. For context this is the dangers of plugin solar I Australia. The max a system can output is 800W. Most households will have 2.5mm cable with 16A or 20A breakers.

    There's a couple of concerns which I'll put in replies.

    💬 2🔄 1⭐ 0

Replies

  • Nov 13, 2026, 5:38 AM

    The first concern is that a user has one plug in solar system, that's running at the max output of 800W. So with combined breaker current limit, plus the current from the plugin solar, it's possible to draw over the intended current capacity for the houses wiring for a segment of the cabling.

    I don't think this is a huge concern as cabling doesn't instantly catch fire at the rating, most users aren't hitting anywhere the limit of their circuit breaker, and when the solar does turn off from darkness the breaker will trip.

    Based on no issues on other countries, this I think is fine.

    💬 0🔄 0⭐ 2
  • Nov 13, 2026, 5:43 AM

    The other scenario is multiple units plugged in to the same circuit. I don't really feel like like this scenario is likely to cause issues either. The user has to ignore warnings, and then if they do, I suspect you'd need like 4 of these at max output to actually cause a serious incident, which just isn't practical for the people who would be buying and using them. And to cause an issue you'd probably need both 4 of them and a decent load before the breaker.

    I haven't done the maths or any experiments but I suspect its one of those things that could be an issue if someone ignored instructions and created a very rare situation.

    💬 2🔄 0⭐ 1
  • Nov 13, 2026, 5:59 AM

    I guess the question comes down to safety margins. This allows a user to eat into the safety margin. Is someone doing the wrong thing suitable to eat into the margin and by how much?

    I think there's enough evidence from other countries that it's not an issue. I'm more concerned of mechanical mounting and panels falling (but that's so minimal to me)

    💬 0🔄 0⭐ 5
  • Nov 13, 2026, 6:11 AM

    So most electricians are very good at knowing the rules, and following the rules to make installs safe. This is good. You should trust them for doing electrical work.

    But engineering the rules, understanding the margins and risk analysis, less so. Their opinions still mater but need to test and validate the concerns.

    💬 0🔄 0⭐ 5
  • Colinabstractcode@eigenmagic.net
    Nov 13, 2026, 5:34 AM

    @xssfox Michaela worried other people might get to eat the spicy electrons?

    💬 0🔄 0⭐ 0
  • Nov 13, 2026, 5:46 AM

    I feel like they should have standardized a power line signalling system that allowed detecting another unit on the same circuit. Though how to get that to work with apartment power being so close, I'm not sure

    💬 0🔄 0⭐ 0
  • Gusprojectgus@aus.social
    Nov 13, 2026, 5:49 AM

    @xssfox One thing I've seen discussed about running EV chargers off outdoor 10A sockets (although that's starting at 2x the power) is that many older outdoor GPOs have quietly been oxidising for decades, and aren't really ready to run continuously for many hours.

    Probably more of a problem at 10A than 3.5A though (and I reckon it's one of the reasons that new cars seem to often come with 6A or 8A slow chargers nowadays.)

    💬 2🔄 0⭐ 0
  • Nov 13, 2026, 5:53 AM

    @projectgus oh interesting. Curious to know the cause of that.

    I suspect if we reinvented power sockets today they'd have thermal fuses built in

    💬 0🔄 0⭐ 0
  • Gusprojectgus@aus.social
    Nov 13, 2026, 5:56 AM

    @xssfox It's only something I've seen discussed anecdotally, so may not be as much of an issue as it was presented as.

    But it kind of makes sense to me that the contacts inside an 40+ year old outdoor outlet may have some resistance that wasn't there when they were clean and new.

    💬 2🔄 0⭐ 0
  • 💬 1🔄 0⭐ 0
  • 💬 1🔄 0⭐ 0
  • 💬 0🔄 0⭐ 0
  • Nov 13, 2026, 6:03 AM

    @projectgus @xssfox
    yeah, our ~90s vintage outdoor outlet and plug got what I'd call hot, but not discolouring or melting plastic hot, when charging the Ioniq with its slow charger (1.4kW).

    Worse, when we first went to use the Zappi unit (7kW) it kept blowing the breaker, turned out the installers didn't tighten the terminals on the breaker 🤦

    💬 0🔄 0⭐ 0
  • Gusprojectgus@aus.social
    Nov 13, 2026, 6:21 AM

    @pwarren @xssfox Spicy breaker!

    When we got a battery the installers did not initially connect Earth to Neutral behind the breaker box...

    Thankfully our EV charger immediately detected this as an earth fault, and after a bit of "nah mate that's some weird problem with your charger, better call the company" they sheepishly acknowledged that they had screwed up pretty bad...

    💬 0🔄 0⭐ 0
  • Nov 13, 2026, 6:01 AM

    @projectgus @xssfox the car chargers also come with some limitations like the US code only allows drawing 80% of rated capacity for continuous use, and that is likely to contribute to software limiting to 8amp

    💬 0🔄 0⭐ 1
  • Gusprojectgus@aus.social
    Nov 13, 2026, 6:29 AM

    @lilstevie @xssfox Yeah, it's definitely a safety margin some manufacturers have put in for some reason (and voluntarily in our case!)

    💬 0🔄 0⭐ 0