    When connecting DC MCBs to stranded cable use crimped bootlace ferrules on the cable to ensure a reliable and low impedance connection. Also ensure that the connections are properly torqued. As a guide MCBs up to 63A should be torqued to about 1.8Nm and those up to 125A 3Nm. Where possible check manufacturer’s data.

    6/n

    #offgrid #battery #breaker